Features
- Achieved by remote monitoring system.
- Over 90 Power and energy parameters
- For Factory and Building Automation
- PLC ModBus®compatible
- 5 A / 1 A Auto-Range
- Max. 600V auto-range 10~150V/600V
- True RMS conversion
- Instant Maximum & Minimum
- VFD display Clear and long-life
- Build in RTC (Real Time Clock)
- Field programmable PT/CT ratio
- Accuracy up to 0.15 %
- Maximum demand control applicable
- Memory for all setup and energy data
- Comprehensive self test diagnostics
- Low input burden 0.1 VA (5A/120V) Wide power supply range 80~260
- VAC/VDC
- Compact physical configuration
- Compatible for DIN & ANSI cut-out 2 KV RMS input/output/power isolation
|
|
Model & Ordering
 |
|
Specification
Input
- Range
- Voltage : maximum 600V, auto range 10 - 150V / 150.1- 600V
- Current : maximum 6A, auto range 0 - 1.5A / 1.51 - 6A, Suitable for CT secondary 5A and 1A
- Frequency 40-70Hz
- Burden
- Voltage < 0.4VA at 600V, < 0.04VA at 150V
- Current < 0.1VA at 5A
- Overload rating
|
|