SPT

HOME > Power System > Power Transducer > Digital Power Transducer > Digital Power Transducer for Industry > Digital Power Transducer - SP Series > SPT

 

Model & Ordering
    SPT-1 ...... single output
    SPT-2 ...... dual outputs
Specification
  • Accuracy : 0.3% RO / 23 + 3 oC
  • Input ( each element ) :
    • RTD input :
      • SP - 1 - PT / SPT - 2 - PT ... PT 100 / 0oC
      • SP - 2 - CU / SPT - 2 - PT ... CU 10 / 25oC
      • Configuration ...... three wires
      • Exciting ...... DC constant current
    • T / C input :
      • SP - 1 - J or K or E or T or N
      • SP - 2 - J or K or E or T or N
      • Sensing module : plug-in type selectable ...... J / K / E / T / N
      • Configuration : Cold junction compensation & linearization
      • Over capability : 250VAC ...... 30 sec
    • Range :
      • Degree C or F : 0 - 50 / 0 - 100 / 0 - 120 / 0 - 200 / 0 - 300 / 0 - 500 / 0 - 600 / 0 - 800 / 0 - 1000 / 0 - 1200 / 0 - 1500 / 0 - 2000 / 0 - 2250 or required specifing
      • Effective Range :
        • PT 100 ... -100 ~ 400C / -150 ~ 800
        • CU 10 ... -100 ~ 400C / -150 ~ 800F
        • J ... -100 ~ 750C / -150 ~ 1400F
        • K ... -100 ~ 1250C / -150 ~ 2250F
        • N ... -100 ~ 1250C / -150 ~ 2250F
      • Full protection for SURGE, EMI & RFI
  • Output ( dual outputs isolated each other > DC600V isolation) :
    • Model SPT - 1 - PT, CU, J, K, E, T, N
    • Model SPT - 2 - PT, CU, J, K, E, T, N
    • Range :
      • DC 0 - 1 / 0 - 5 / 1 - 5 / 0 - 10 / 0 - 20 / 4 - 20mA
      • DC 0 - 1 / 0 - 5 / 1 - 5 / 0 - 10 / 2 - 10V
      • Standard calibation 0 - 1mA vs required input range
      • Option calibration under required input range
    • Drive ability :
      • > 10Kohm for 0 to 1mA standard output
      • > 10V for current output mode
      • > 10mA for voltage output mode
    • Output impedance > 30 Mega ohm
    • Response time < 400 ms from 0 to 99% RO at operating
    • Ripple < 0.5% P-P RO
    • Long term stability < 0.3% RO per year
    • Temperature stability :
      • RTD ... 0.012% of range / oC or 0.03oC / oC ... which ever great
      • T / C ... 0.012% of range / oC or 0.05oC / oC ... which ever great
    • Adjustment : Span, zero +5% ro minimum or under required
    • Protection : No damage ... open or short; full protection ... SURGE, EMI, RFI
    • Magnetic effection < 0.04% at center 400 A-T / M
  • Operation Condition :
    • Enviroment Temperature : -5 ~ 60 oC
    • Humidity : 20~99% RH non condensed
    • Elevation : Under 3000 meters
    • Magnetic Field : 500 A-T / M
    • Waveform : Sinusoidual
    • Dielectric strength : 4KV AC rms 1 minute between input / output / power / case IEC688
    • Impulse Test : ANSI C37.90 / 1989, IEEE 587 / 1983, IEC 255-3 ( 1.2 * 50us), 3KA (8 * 20us)... current only
    • Surge Test (ring wave) : IEEE 587 / 1983 (3KV - 0.5 us / 100 KHz), IEC255-3 (2.5KV - 0.25ms / 1MHz)
    • Power Supply : AC 115V + 20%, 50 - 70Hz, < 3VA, Option AC 230V, DC 12 / 24 / 48 / 125V