Features
- Linearized output
- Field - rangeable :
- Switchable input & output ranges
- Changeable input T/C module P1 / P4 / P8 / C4
- Accuracy 0.15%
- Input / output isolation 1.6KVdc
- Available standard calibration or custom calibration
|
|
Model & Ordering
 |
|
Specification
- Accuracy ( 23 + 3 oC ) :
- 0.15% of effective range + 0.3oC..... P4 / P8
- 0.25% of effective range + 0.15oC ..... P1 / CU
- Linearty & repeatability : 0.1% typical
- Temperature stability < 0.01% fs per degree C
- Configuration :
- Three wires connection / applicable for two wires
- Excitation ... 5 mAdc constant current soure
- Change input module
- Field rangeability :
- Selectable output mode.....voltage or current
- Switchable input ranges/switchable output ranges
- Switchable AC power 120V or 240V
- selectable oC / oF calibration
- Effect of wire resistance :
- Automatically eliminated for 3 wires connection
- Offset recal. required for 2 wires connection
- Input break detection : Hi - set >110% of rated output
- Maximum input over : <250 Vrms 30 sec.
- Power effect < 0.003% for per volt change
- Response time & ripple : 250ms typically , ripple < 0.1% rms of span
- Output drive capability <10mA for voltage mode, <10 V for current mode
- Common mode rejection > 100db, 50 / 60 Hz
- Dielectric strength :
- 1500Vac ..... power / input & output terminals
- 1600Vdc ..... input / output terminals
- Storage condition : Temperature range -10 ~ 70oC, humidity 20~95% RH non - condensed
- Operating condition : Temperature range -5 ~ 55oC, humidity 20~95% RH non - condensed
- Power supply :
- + 20% of rated , less 3.5 VA for AC input
- + 20% of rated , less 3.5 watt for DC input
- Construction : Socket plug - in type with barrier terminals
|
|