HOME > Power System > Power Transducer > Digital Power Transducer > Digital Power Transducer for Industry > Digital Power Transducer - PS Series > PSF

 

 

Features
  • Wide switchable input ranges 0 to 10 ~ 10 KHZ
  • Wide switchable output ranges
  • With discriminator - adjustable input sensitivity
  • With intensed filter-selectable
  • F-V / crystal heart conversion long term stability guaranteed
  • 0.1% accuracy
Model & Ordering

        

Specification
  • Accuracy ( 23 + 3 oC ) : 0.1% of rated output
  • Linearty & repeatability : 0.05% typical
  • Temperature stability < 0.008% of range per oC
  • Configuration :
    • Switchable input ranges; switchable output ranges
    • +5% adjustability.....fine span & zero
  • Power effect < 0.003% for per volt change
  • Response time :
    • < 800ms typical........non intensed filter on
    • < 4 seconds..............intensed filter on
    • < 0.05% / Fin ( Fin.......unit khz )
  • Input sensing :
    • Input types
    • Voltage.........unipolar / bipolar
    • Signal ...........square pulse or sinusoidal signal, open collector
    • Sensitivity.......10 mV to 5V adjustable; 1 V at factory calibration
    • Maximum over........100 V continuous.....400V 1 sec
  • Excitation : +12 VDC, drive capability 20 mA maximum
  • Output drive <10mA for voltage mode, <10 V for current mode
  • Dielectric strength :
    • 1500Vac ..... power / input & output terminals
    • 1600Vdc ..... input / output terminals
  • Operating condition : Temperature range -5 ~ 55oC, humidity 20~95% RH non - condensed
  • Storage condition : Temperature range -10 ~ 70oC, humidity 20~95% RH non - condensed
  • Power supply :
    • + 20% of rated , less 3.5 VA for AC input
    • + 20% of rated , less 3.5 watt for DC input
  • Construction : Socket plug - in type with barrier terminals