HOME > Power System > Power Transducer > Digital Power Transducer > Digital Power Transducer for Industry > Digital Power Transducer - PP Series > PPFV

 

Model & Ordering

      

Specification
  • Accuracy ( 23 + 5 oC ) :0.1% RO
  • Linearty & repeatability : 0.05% typical
  • Temperature stability : Less 0.008% ro per degree C effective range
  • Maximum input over : Voltage input
    • 1.5 * rated / continuous
    • 2 * rated / 10 seconds
  • Dielectric strength : 4KV AC rms 1 minute between input / output / power / case IEC 688
  • Impulse test : ANSI C37.90a / 1974, IEEE 587 / 1983, IEC 255-3 6KV (1.2 * 50 us)
  • Surge test (ring wave) : IEEE 587 / 1983 (3KV~0.5us / 100KHz), IEC 255-3 (2.5KV~0.25ms / 1MHz)
  • Configuration :
    • Switchable of input ranges & output ranges
    • +15% adjustability of fine span & zero
  • Power effect : Less 0.003% for per volt change
  • Input sensing :
    • Input type both of plus unipolar or bipolar
    • Waveform square pulse or sinusoidal signal or open collector
    • Sensitivity 10mV to 5V adjustable 1V in factor preadjust
    • Maximum over 100V continuous, 400V 1sec
  • Excitation : +12Vdc, drive capability 20mA maximum
  • Output drive capability : Less 10mA for voltage mode, 10V for current mode
  • Response time & ripple : Less 400ms typically, ripple less 0.1% rms of span
  • Common mode rejection > 100db, 50 / 60Hz
  • Dielectric strength : 4KV rms AC between input / output / power / case
  • Impulse & surge test : IEEE 587 / 1983 or IEC 255-3
  • Storage condition : Temperature range -25 to +70oC, RH 20 to 95% non condensed
  • Operating condition : Temperature range -20 to +65oC, RH 20 to 95% non condensed
  • Power supply : +20% of rating < 3.5VA
  • Dimension : W*H*D : 12T (60.6mm) * 3U (128.5mm) * 238mm