Model & Ordering
 |
|
Specification
- Accuracy ( 23 + 5 oC ) : 0.2% RO
- Linearty & repeatability :
- 0.12% typical
- Linearized output vs input temperature
- Temperature stability : Less 0.01% fs per degree C
- Configuration :
- Field rangeability
- Changeable thermocouple input module
- Selectable output for voltage or current mode
- Switchable input & output ranges
- Switchable AC power for 110V or 220V
- Selectable C / F calibration
- CJC stability : Less 0.03oC per oC, 10 to 40o
- CJC traceability :
- Warm up condition, typically
- Less 0.5oC deviation in 10 minutes
- Input resistance : Minimum 20M

- Effect of wire resistance : Less 4 uV per 100

- Input break detection :
- Selectable Hi-set or Lo-set
- Hi-set over 110% of rated output
- Lo-set less 0.5% of rated output
- Maximum input over : Maximum 250V rms 30 sec
- Power effect : Less 0.003% for per volt change
- Response time & ripple : Less 400ms typically, ripple less 0.15% rms of span
- Common mode rejection > 100db 50 / 60Hz
- Dielectric strength :
- 4KV AC rms 1 minute between terminals to case IEC 688
- 2KV AC rms 1 minute between input / output / power IEC 688
- Impulse & surge test : ANSI C37.90 / 1989, IEC 255-3
- Output drive capability : Maximum 5mA for voltage mode, maximum 10V for current mode
- Storage condition : Temperature range -25 to +70oC, RH 20 to 95% non condensed
- Operating condition : Temperature range -20 to +65oC, RH 20 to 95% non condensed
- Power supply : +20% of rating, less 5VA
- Dimension : W*H*D : 12T (60.6mm) * 3U (128.5mm) * 238mm
|
|