Model & Ordering
 |
|
Specification
- Accuracy ( 23 + 3 oC ) : 0.3% ro
- Linearty & repeatability : 0.1% typical
- Dielectric strength : 4KV rms AC between power / input & output terminals
- Output drive capability : <10mA for voltage mode, <10V for current mode
- Surge and impulse test : ANSI C37.90 / 1989, IEC 255-3 (1989) 4 KV 1.2 * 50 us
- Configuration :
- Three wires connection / applicable for two wires
- Excitation - 5mAdc constant current source
- Changeable input module
- Linearized output vs input temperature
- Field rangeability :
- Selectable output mode for voltage or current mode
- Switchable of input range & output range
- Switchable AC power 110V or 220V
- Selectable degree C or F calibration
- Effect of wire resistance :
- Automatically eliminated for 3 wires connection
- Offset recalibration required as for 2 wires connection
- Input break detection :
- Selectable Hi-set or Lo-set
- Hi-set over 110% of rated output
- Lo-set less 0.5% of rated output
- Aux. power effect : < 0.003% for per voltage change
- Storage condition : Temperature range -25 to 70oC, RH 20 to 95% non condensed
- Operating condition : Temperature range -20 to 65oC, RH 0 to 99% non condensed
|
|
|
|
|
|