FPD / FPDH

HOME > Power System > Power Transducer > Digital Power Transducer > Digital Power Transducer for Industry > Digital Power Transducer - FP Series > FPD / FPDH

 

Model & Ordering

      

Specification
  • Accuracy ( 23 + 3 oC ) : 0.25% of effecive range
  • Linearty & repeatability : 0.05% typical
  • Dielectric strength :
    • 1500Vac ... power / input & output terminals .... FPD
    • 1800Vac ... input / output / case .......................... FPD
    • 2000Vac ... power / input & output terminals .... FPDH
    • 2500Vac ... input / output / case .......................... FPDH
  • Output drive capability : <10mA for voltage mode, <10V for current mode
  • Maximum input over :
    • <300Vrms continuous ... > 2V ranges
    • <150Vrms continuous ... <2V ranges
    • <150mA continuous for current input
  • Input resistance-ohm :
    • >100M ... <2V ranges, >500K ... >2V ranges
    • <20 ... for all current input ranges
  • Power effect : < 0.003% for per volt change
  • Response time & ripple : 250 ms typically, ripple < 0.1% rms ro
  • Common mode rejection : 120dB, DC to 60Hz
  • Temperatured stability : < 0.007% ro per degree C
  • Storage condition : Temperature range -10 to 70oC, RH 20 to 95% non condensed
  • Operating condition : Temperature range -5 to 55oC, RH 20 to 95% non condensed
  • Power supply :
    • +10% of rated, less 3.5 VA for AC input
    • +10% of rated, less 3.5 Watt for DC input
  • Construction : Socket plug-in type with barrier terminals