Description
HC power voltage transducers are with reading base accuracy conversion ideally applied for an accuracte
measurement of AC voltage input, with self power mode of non external power design to simpliz wire
connection particularly useful for user in field application.
Models are available for one voltage & three voltage units with average responding scaled to RMS output.
|
|
Specification
- Accuracy : 0.25% RD + 0.02%RO / 23 + 3 oC
- Input ( each element ) :
- Range : Effective voltage 0 - 165V; nominal voltage 120V
- Over capability : 200V continuous 250V ... 10sec / hour; 300V ... 5sec / hour
- Burden : voltage < 3VA at 120V input
- Frequency : 50 - 70Hz
- Protection : Full protection for SURGE, EMI & RFI
- Output ( isolated with input ) :
- Range :
- Standard DC 0 to + 1mA
- DC 0 to +1mA calibration vs 0 to 150V
- Output load : Maximum 10Kohm for 0 to 1 mA ouput
- Output impedance > 30 Mega ohm
- Response time < 400 ms from 0 to 99% RO at operating
- Ripple < 0.5% P-P RO
- Long term stability < 0.1% RO per year ( typically )
- Temperature stability < 0.01% per degree C, from 0 to 55oC
- Adjustment : Span +5% / 10%; zero ... non
- Protection : No damage ... open or short; full protection ... SURGE, EMI, RFI
- Magnetic effection < 0.04% at center 400 A-T / M
- Operation Condition :
- Enviroment Temperature : -5 ~ 60 oC
- Humidity : 20~99% RH non condensed
- Elevation : Under 3000 meters
- Magnetic Field : 500 A-T / M
- Waveform : Sinusoidual
- Dielectric strength : 4KV AC rms 1 minute between input / output / power / case IEC688
- Impulse Test : ANSI C37.90 / 1989, IEEE 587 / 1983, IEC255-3, 6KV (1.2 * 50 us), 3KA (8 * 20 us) ..... current only
- Surge Test (ring wave) : IEEE 587 / 1983 (3KV - 0.5 us / 100 KHz), IEC255-3 (2.5KV - 0.25ms / 1MHz)
|
|