PPV / PPVR

HOME > Power System > Power Transducer > Digital Power Transducer > Digital Power Transducer for Utility > Digital Power Transducer - PP Series > PPV / PPVR

 

Model & Ordering

      

Specification
  • Accuracy ( 23 + 5 oC ) :
    • 0.25% RD + 0.02% RO ........ PPA, PPAX, PPV, PPVX
    • 0.3% RO ........ PPAR, PPVR
  • Maximum output load : Maximum 10V drive for current output mode, maximum 10mA for voltage output mode
  • Output of WH & VarH : Open collecter type, maximum 50V / 30mA
  • Dielectric strength : 4KV AC rms 1 minute between input / output / power / case IEC 688
  • Impulse test : ANSI C37.90a / 1974, IEEE 587 / 1983, IEC 255-3 6KV (1.2 * 50 us), 3KA (8 * 20 us) ..... current only
  • Surge test (ring wave) : IEEE 587 / 1983 (3KV~0.5us / 100KHz), IEC 255-3 (2.5KV~0.25ms / 1MHz)
  • Maximum input over :
  •       
  • Input burden :
    • Current / less 0.2VA, voltage / less 0.25VA per element
    • 1VA per element ........ self power for V & A
  • Power effect : Less 0.003% for per volt change
  • Response time & ripple : Less 400ms typically, ripple less 0.5% ro peak to peak
  • Frequency : 48 to 65 Hz
  • Waveform : Sinusoidal
  • Stability : Temperature range ( -10 to +60oC ), less 100 ppm degree C
  • Output calibration :
    • Minimum span +3% / zero +0.5% for 0~1mA type
    • Minimum span +3% / zero +3% for 4~20mA type
  • Storage condition : Temperature range -25 to +70oC, RH 20 to 95% non condensed
  • Operating condition : Temperature range -20 to +65oC, RH 20 to 95% non condensed
  • Magnetic field effect : Less 0.02% under 100 ampere -turns, at 1M center
  • Power dissipation : Maximum 3.5VA for PPA / PPAR / PPV / PPVR; 8VA for PPAX / PPVX
  • Dimension : W*H*D : 12T (60.6mm) * 3U (128.5mm) * 238mm