PPF

HOME > Power System > Power Transducer > Digital Power Transducer > Digital Power Transducer for Utility > Digital Power Transducer - PP Series > PPF

 

Model & Ordering

      

Specification
  • Accuracy ( 23 + 5 oC ) : 0.025% of named frequency + 0.02% RO
  • Maximum output load :
    • Maximum 10V drive for current output mode
    • Maximum 10mA for voltage output mode
  • Dielectric strength : 4KV AC rms 1 minute between input / output / power / case IEC 688
  • Impulse test : ANSI C37.90a / 1974, IEEE 587 / 1983, IEC 255-3 6KV (1.2 * 50 us)
  • Surge test (ring wave) : IEEE 587 / 1983 (3KV~0.5us / 100KHz), IEC 255-3 (2.5KV~0.25ms / 1MHz)
  • Maximum input over : Voltage input
    • 1.5 * rated / continuous
    • 2 * rated / 10 seconds
  • Input burden : Voltage / less 0.1VA, self power / less 3VA per element
  • Power effect : Less 0.003% for per volt change
  • Response time & ripple : Less 400ms typically, ripple less 0.5% ro peak to peak
  • Frequency : 50; 60 Hz
  • Waveform : Sinusoidal
  • Stability :
    • Temperature range (-10 to +60oC), long term stabiliy / year
    • Maximum 100 ppm degree C, less 0.1% drift
  • Output calibration :
    • Minimum span +3% / zero +0.5% for 0~1mA type
    • Minimum span +3% / zero +3% for 4~20mA type
  • Storage condition : Temperature range -25 to +70oC, RH 20 to 95% non condensed
  • Operating condition : Temperature range -20 to +65oC, RH 20 to 95% non condensed
  • Magnetic field effect : Magnetic field effect, less 0.02% under 100 ampere -turns, at 1M center
  • Power dissipation : Maximum 3.5VA
  • Dimension : W*H*D : 12T (60.6mm) * 3U (128.5mm) * 238mm