PP1PF

HOME > Power System > Power Transducer > Digital Power Transducer > Digital Power Transducer for Utility > Digital Power Transducer - PP1 Series > PP1PF

 

Model & Ordering

      

Specification
  • Accuracy ( 23 + 5 oC ) : 0.2% RO + 0.3o
  • Maximum output load :
    • Maximum 10V drive for current output mode, maximum 5mA for voltage output mode
    • Maximum 5mA for voltage output mode
  • Dielectric strength :
    • 4KV AC rms 1 minute between terminals to case IEC 688
    • 2KV AC rms 1 minute between input / output / power IEC 688
  • Impulse test : ANSI C37.90 / 1989, IEC 255-3 5KV ( 1.2 * 50 us ), 3KA ( 8 * 20 us ) ..... current only
  • Surge test (ring wave) : ANSI C37.90 / 1989 ( 3KV~0.5us / 100KHz ), IEC 255-3 ( 2.5KV~0.25ms / 1MHz )
  • Maximum input over :
  •       
  • Input burden : Current / less 0.2VA, voltage / less 0.1VA
  • Power effect : Less 0.003% for per volt change
  • Response time & ripple : Less 400ms typically, ripple less 0.5% ro peak to peak
  • Frequency : 50 +3, 60 +3 Hz
  • Waveform : Sinusoidal
  • Stability : Temperature range ( -10 to +60oC ), less 100 ppm per degree C
  • Storage condition : Temperature range -25 to +70oC, RH 20 to 95% non condensed
  • Operating condition : Temperature range -20 to +65oC, RH 20 to 95% non condensed
  • Magnetic field effect : Less 0.02% under 100 ampere -turns, at 1M center
  • Power dissipation : Maximum 3.5VA
  • Dimension : W*H*D : 12T (60.6mm) * 3U (128.5mm) * 238mm