HOME > Power System > Power Meter > Digital Power Meter > Digital Power Meter for Utility > Digital Power Meter - MP / ML

Model MP & ML Power factor and Phase angle meters, designed of a balance type with universal & flexible application feature, can be applied to measure single phase 2 or 3 wires, 3 phase 3 wires & 3 phase 4 wires only under the specified terminal connection. The units accept ac voltage & current inputs with detection of phase relation between the measured phase voltage & phase current of power factor COSØ for MP & phase angle for ML. The designed specifications compliant ANSI, DIN & VDE standards with full protection for unusual surge intrusion and input over assuring reliable operation.
Digital Power Meter - MP / ML

 

Features
  • True power system design compliants ANSI-IEEE, IEC & VDE standards
  • High over capability to assure reliable operation
  • High accuracy 0.5%
  • Display with super rate LED
Model & Ordering

      

Specification
  • Accuracy (23 + 3oC) : 0.5%fs + 0.2o > 20% input current, 0.5%fs + 0.4o >10% input current
  • Stability : Temperature coefficient <50 ppm per degree c, long term draft <0.2% per year
  • Digits & resolution : 0.56" super rate LED, 0.001 - 0.999 for PF, 0.010 - 360.0 degree for phase angle
  • Display : 0.56" super rate LED
  • Response time : Sample rate 1 of per sec. typically
  • Input over :
    • Current input : 3 * rating-continuous, 10 * rating-30 sec., 25 * rating-3 sec.
    • Voltage input : max continuous 750V or 1.5 rating which ever great
  • Frequency : 47-70 Hz
  • Dielectric strength : 2.5KV rms / 1 min, all terminals to case, 2KVrms / 1 min input vs power terminals
  • Surge test : ANSI C37.90 / 1989, IEC 255-3 (1989)
  • Impulse voltage : 1.2 * 50 us 4 kv, oscillation wave 0.5us-100KHz 3KV, or 1 MHz-0.25ms 2.5KV
  • Operating condition : -10 to 55oC, 0-99% RH non-condensed
  • Storage condition : -25 to 70oC
  • Auxiliary power : AC + 15% < 6 VA, DC + 20% < 6 watts